Skip to content
CVE PROGRAM SOURCE RECORD5.9 Medium

CVE-2026-17539

RTU500 has a vulnerability, where high-load scenarios, such as sending GI requests at short intervals, may cause a NULL pointer dereference in the last entry of the enhanced messag

Description

RTU500 has a vulnerability, where high-load scenarios, such as sending GI requests at short intervals, may cause a NULL pointer dereference in the last entry of the enhanced message queue. This can cause a BCI_IEC104 fatal write error, resulting in connection interruption and restart, and ultimately a denial of service for bidirectional IEC 60870-5-104 communication.

Affected products

Version statuses are supplied by the assigning organization. Consult the original record for detailed ranges and platform conditions.

Hitachi Energy RTU500 series CMU firmware

Default version status: unaffected

  • 12.7.1 to ≤ 12.7.7affected
  • 13.5.1 to ≤ 13.5.4affected
  • 13.6.1 to ≤ 13.6.3affected
  • 13.7.1 to ≤ 13.7.8affected
  • 13.8.1 to ≤ 13.8.2affected

References