Description
RTU500 has a vulnerability, where high-load scenarios, such as sending GI requests at short intervals, may cause a NULL pointer dereference in the last entry of the enhanced message queue. This can cause a BCI_IEC104 fatal write error, resulting in connection interruption and restart, and ultimately a denial of service for bidirectional IEC 60870-5-104 communication.
Affected products
Version statuses are supplied by the assigning organization. Consult the original record for detailed ranges and platform conditions.
Hitachi Energy RTU500 series CMU firmware
Default version status: unaffected
12.7.1 to ≤ 12.7.7affected13.5.1 to ≤ 13.5.4affected13.6.1 to ≤ 13.6.3affected13.7.1 to ≤ 13.7.8affected13.8.1 to ≤ 13.8.2affected