Skip to content
CVE PROGRAM SOURCE RECORD8.7 High

CVE-2025-9041

Rockwell Automation FLEX 5000 I/O - Module Fault

Description

A security issue exists due to improper handling of CIP Class 32’s request when a module is inhibited on the 5094-IF8 device. It causes the module to enter a fault state with the Module LED flashing red. Upon un-inhibiting, the module returns a connection fault (Code 16#0010), and the module cannot recover without a power cycle.

Affected products

Version statuses are supplied by the assigning organization. Consult the original record for detailed ranges and platform conditions.

Rockwell Automation FLEX 5000 I/O

Default version status: unaffected

  • Version 2.011 or belowaffected

References