Description
A security issue exists due to improper handling of malformed CIP Forward Close packets during fuzzing. The controller enters a solid red Fault LED state and becomes unresponsive. Upon power cycle, the controller will enter recoverable fault where the MS LED and Fault LED become flashing red and reports fault code 0xF015. To recover, clear the fault.
Affected products
Version statuses are supplied by the assigning organization. Consult the original record for detailed ranges and platform conditions.
Rockwell Automation PLC - Micro850 L50E
Default version status: unaffected
V20.011 - V22.011affected