Description
A vulnerability has been identified in SIMATIC ET 200AL IM 157-1 PN (6ES7157-1AB00-0AB0) (All versions), SIMATIC ET 200MP IM 155-5 PN HF (6ES7155-5AA00-0AC0) (All versions >= V4.2.0), SIMATIC ET 200SP IM 155-6 MF HF (6ES7155-6MU00-0CN0) (All versions), SIMATIC ET 200SP IM 155-6 PN HA (incl. SIPLUS variants) (All versions < V1.3), SIMATIC ET 200SP IM 155-6 PN R1 (6ES7155-6AU00-0HM0) (All versions < V6.0.1), SIMATIC ET 200SP IM 155-6 PN/2 HF (6ES7155-6AU01-0CN0) (All versions >= V4.2.0 < V4.2.5), SIMATIC ET 200SP IM 155-6 PN/3 HF (6ES7155-6AU30-0CN0) (All versions < V4.2.2), SIMATIC PN/MF Coupler (6ES7158-3MU10-0XA0) (All versions), SIMATIC PN/PN Coupler (6ES7158-3AD10-0XA0) (All versions < V6.0.0), SIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-2AC0) (All versions >= V4.2.0), SIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-7AC0) (All versions >= V4.2.0), SIPLUS ET 200MP IM 155-5 PN HF T1 RAIL (6AG2155-5AA00-1AC0) (All versions >= V4.2.0), SIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU01-2CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU01-7CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS ET 200SP IM 155-6 PN HF T1 RAIL (6AG2155-6AU01-1CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS ET 200SP IM 155-6 PN HF TX RAIL (6AG2155-6AU01-4CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS NET PN/PN Coupler (6AG2158-3AD10-4XA0) (All versions < V6.0.0). Affected devices do not properly handle S7 protocol session disconnect requests. When receiving a valid S7 protocol Disconnect Request (COTP DR TPDU) on TCP port 102, the devices enter an improper session state. This could allow an attacker to cause the device to become unresponsive, leading to a denial-of-service condition that requires a power cycle to restore normal operation.
Affected products
Version statuses are supplied by the assigning organization. Consult the original record for detailed ranges and platform conditions.
Siemens SIMATIC ET 200AL IM 157-1 PN
Default version status: unknown
0 to < *affected
Siemens SIMATIC ET 200MP IM 155-5 PN HF
Default version status: unknown
V4.2.0 to < *affected
Siemens SIMATIC ET 200SP IM 155-6 MF HF
Default version status: unknown
0 to < *affected
Siemens SIMATIC ET 200SP IM 155-6 PN HA (incl. SIPLUS variants)
Default version status: unknown
0 to < V1.3affected
Siemens SIMATIC ET 200SP IM 155-6 PN R1
Default version status: unknown
0 to < V6.0.1affected
Siemens SIMATIC ET 200SP IM 155-6 PN/2 HF
Default version status: unknown
V4.2.0 to < V4.2.5affected
Siemens SIMATIC ET 200SP IM 155-6 PN/3 HF
Default version status: unknown
0 to < V4.2.2affected
Siemens SIMATIC PN/MF Coupler
Default version status: unknown
0 to < *affected
Siemens SIMATIC PN/PN Coupler
Default version status: unknown
0 to < V6.0.0affected
Siemens SIPLUS ET 200MP IM 155-5 PN HF
Default version status: unknown
V4.2.0 to < *affected
Siemens SIPLUS ET 200MP IM 155-5 PN HF
Default version status: unknown
V4.2.0 to < *affected
Siemens SIPLUS ET 200MP IM 155-5 PN HF T1 RAIL
Default version status: unknown
V4.2.0 to < *affected
Siemens SIPLUS ET 200SP IM 155-6 PN HF
Default version status: unknown
V4.2.0 to < V4.2.5affected
Siemens SIPLUS ET 200SP IM 155-6 PN HF
Default version status: unknown
V4.2.0 to < V4.2.5affected
Siemens SIPLUS ET 200SP IM 155-6 PN HF T1 RAIL
Default version status: unknown
V4.2.0 to < V4.2.5affected
Siemens SIPLUS ET 200SP IM 155-6 PN HF TX RAIL
Default version status: unknown
V4.2.0 to < V4.2.5affected
Siemens SIPLUS NET PN/PN Coupler
Default version status: unknown
0 to < V6.0.0affected