Skip to content
CVE PROGRAM SOURCE RECORD8.7 High

CVE-2025-40944

A vulnerability has been identified in SIMATIC ET 200AL IM 157-1 PN (6ES7157-1AB00-0AB0) (All versions), SIMATIC ET 200MP IM 155-5 PN HF (6ES7155-5AA00-0AC0) (All versions >= V4.2.

Description

A vulnerability has been identified in SIMATIC ET 200AL IM 157-1 PN (6ES7157-1AB00-0AB0) (All versions), SIMATIC ET 200MP IM 155-5 PN HF (6ES7155-5AA00-0AC0) (All versions >= V4.2.0), SIMATIC ET 200SP IM 155-6 MF HF (6ES7155-6MU00-0CN0) (All versions), SIMATIC ET 200SP IM 155-6 PN HA (incl. SIPLUS variants) (All versions < V1.3), SIMATIC ET 200SP IM 155-6 PN R1 (6ES7155-6AU00-0HM0) (All versions < V6.0.1), SIMATIC ET 200SP IM 155-6 PN/2 HF (6ES7155-6AU01-0CN0) (All versions >= V4.2.0 < V4.2.5), SIMATIC ET 200SP IM 155-6 PN/3 HF (6ES7155-6AU30-0CN0) (All versions < V4.2.2), SIMATIC PN/MF Coupler (6ES7158-3MU10-0XA0) (All versions), SIMATIC PN/PN Coupler (6ES7158-3AD10-0XA0) (All versions < V6.0.0), SIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-2AC0) (All versions >= V4.2.0), SIPLUS ET 200MP IM 155-5 PN HF (6AG1155-5AA00-7AC0) (All versions >= V4.2.0), SIPLUS ET 200MP IM 155-5 PN HF T1 RAIL (6AG2155-5AA00-1AC0) (All versions >= V4.2.0), SIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU01-2CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS ET 200SP IM 155-6 PN HF (6AG1155-6AU01-7CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS ET 200SP IM 155-6 PN HF T1 RAIL (6AG2155-6AU01-1CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS ET 200SP IM 155-6 PN HF TX RAIL (6AG2155-6AU01-4CN0) (All versions >= V4.2.0 < V4.2.5), SIPLUS NET PN/PN Coupler (6AG2158-3AD10-4XA0) (All versions < V6.0.0). Affected devices do not properly handle S7 protocol session disconnect requests. When receiving a valid S7 protocol Disconnect Request (COTP DR TPDU) on TCP port 102, the devices enter an improper session state. This could allow an attacker to cause the device to become unresponsive, leading to a denial-of-service condition that requires a power cycle to restore normal operation.

Affected products

Version statuses are supplied by the assigning organization. Consult the original record for detailed ranges and platform conditions.

Siemens SIMATIC ET 200AL IM 157-1 PN

Default version status: unknown

  • 0 to < *affected

Siemens SIMATIC ET 200MP IM 155-5 PN HF

Default version status: unknown

  • V4.2.0 to < *affected

Siemens SIMATIC ET 200SP IM 155-6 MF HF

Default version status: unknown

  • 0 to < *affected

Siemens SIMATIC ET 200SP IM 155-6 PN HA (incl. SIPLUS variants)

Default version status: unknown

  • 0 to < V1.3affected

Siemens SIMATIC ET 200SP IM 155-6 PN R1

Default version status: unknown

  • 0 to < V6.0.1affected

Siemens SIMATIC ET 200SP IM 155-6 PN/2 HF

Default version status: unknown

  • V4.2.0 to < V4.2.5affected

Siemens SIMATIC ET 200SP IM 155-6 PN/3 HF

Default version status: unknown

  • 0 to < V4.2.2affected

Siemens SIMATIC PN/MF Coupler

Default version status: unknown

  • 0 to < *affected

Siemens SIMATIC PN/PN Coupler

Default version status: unknown

  • 0 to < V6.0.0affected

Siemens SIPLUS ET 200MP IM 155-5 PN HF

Default version status: unknown

  • V4.2.0 to < *affected

Siemens SIPLUS ET 200MP IM 155-5 PN HF

Default version status: unknown

  • V4.2.0 to < *affected

Siemens SIPLUS ET 200MP IM 155-5 PN HF T1 RAIL

Default version status: unknown

  • V4.2.0 to < *affected

Siemens SIPLUS ET 200SP IM 155-6 PN HF

Default version status: unknown

  • V4.2.0 to < V4.2.5affected

Siemens SIPLUS ET 200SP IM 155-6 PN HF

Default version status: unknown

  • V4.2.0 to < V4.2.5affected

Siemens SIPLUS ET 200SP IM 155-6 PN HF T1 RAIL

Default version status: unknown

  • V4.2.0 to < V4.2.5affected

Siemens SIPLUS ET 200SP IM 155-6 PN HF TX RAIL

Default version status: unknown

  • V4.2.0 to < V4.2.5affected

Siemens SIPLUS NET PN/PN Coupler

Default version status: unknown

  • 0 to < V6.0.0affected

References