Description
A weakness in Automated Logic and Carrier i-Vu Gen5 router on driver version drv_gen5_106-01-2380, allows malformed packets to be sent through BACnet MS/TP network causing the devices to enter a fault state. This fault state requires a manual power cycle to return the device to network visibility.
Affected products
Version statuses are supplied by the assigning organization. Consult the original record for detailed ranges and platform conditions.
Automated Logic WebCtrl
Default version status: unaffected
0 to ≤ 8.5affected
Automated Logic Gen5 Controllers
Default version status: unaffected
0 to ≤ drv_gen5_108-04-20120affected
Carrier i-Vu
Default version status: unaffected
0 to ≤ 8.5affected