Description
SAUTER Controls Nova 200–220 Series with firmware version 3.3-006 and prior and BACnetstac version 4.2.1 and prior have only FTP and Telnet available for device management. Any sensitive information communicated through these protocols, such as credentials, is sent in cleartext. An attacker could obtain sensitive information such as user credentials to gain access to the system.
Affected products
Version statuses are supplied by the assigning organization. Consult the original record for detailed ranges and platform conditions.
SAUTER Controls Nova 220 (EYK220F001) DDC with BACnet connection
Default version status: unaffected
Firmware all versions to ≤ 3.3-006affectedBACnetstac all versions to ≤ 4.2.1affected
SAUTER Controls Nova 230 (EYK230F001) DDC with BACnet connection
Default version status: unaffected
Firmware all versions to ≤ 3.3-006affectedBACnetstac all versions to ≤ 4.2.1affected
SAUTER Controls Nova 106 (EYK300F001) BACnet communication card
Default version status: unaffected
Firmware all versions to ≤ 3.3-006affectedBACnetstac all versions to ≤ 4.2.1affected
SAUTER Controls moduNet300 (EY-AM300F001, EY-AM300F002)
Default version status: unaffected
Firmware all versions to ≤ 3.3-006affectedBACnetstac all versions to ≤ 4.2.1affected