Description
A vulnerability exists in HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-3. After session resumption interval is expired an RTU500 initiated update of session parameters causes an unexpected restart due to a stack overflow.
Affected products
Version statuses are supplied by the assigning organization. Consult the original record for detailed ranges and platform conditions.
Hitachi Energy RTU500 series
Default version status: unaffected
RTU500 series CMU Firmware version 13.3.1affectedRTU500 series CMU Firmware version 13.3.2affectedRTU500 series CMU Firmware version 13.3.3unaffectedRTU500 series CMU Firmware version 13.4.1unaffected