Skip to content
CVE PROGRAM SOURCE RECORD7.6 High

CVE-2022-42784

A vulnerability has been identified in LOGO! 12/24RCE (6ED1052-1MD08-0BA1) (All versions >= V8.3), LOGO! 12/24RCEo (6ED1052-2MD08-0BA1) (All versions >= V8.3), LOGO! 230RCE (6ED105

Description

A vulnerability has been identified in LOGO! 12/24RCE (6ED1052-1MD08-0BA1) (All versions >= V8.3), LOGO! 12/24RCEo (6ED1052-2MD08-0BA1) (All versions >= V8.3), LOGO! 230RCE (6ED1052-1FB08-0BA1) (All versions >= V8.3), LOGO! 230RCEo (6ED1052-2FB08-0BA1) (All versions >= V8.3), LOGO! 24CE (6ED1052-1CC08-0BA1) (All versions >= V8.3), LOGO! 24CEo (6ED1052-2CC08-0BA1) (All versions >= V8.3), LOGO! 24RCE (6ED1052-1HB08-0BA1) (All versions >= V8.3), LOGO! 24RCEo (6ED1052-2HB08-0BA1) (All versions >= V8.3), SIPLUS LOGO! 12/24RCE (6AG1052-1MD08-7BA1) (All versions >= V8.3), SIPLUS LOGO! 12/24RCEo (6AG1052-2MD08-7BA1) (All versions >= V8.3), SIPLUS LOGO! 230RCE (6AG1052-1FB08-7BA1) (All versions >= V8.3), SIPLUS LOGO! 230RCEo (6AG1052-2FB08-7BA1) (All versions >= V8.3), SIPLUS LOGO! 24CE (6AG1052-1CC08-7BA1) (All versions >= V8.3), SIPLUS LOGO! 24CEo (6AG1052-2CC08-7BA1) (All versions >= V8.3), SIPLUS LOGO! 24RCE (6AG1052-1HB08-7BA1) (All versions >= V8.3), SIPLUS LOGO! 24RCEo (6AG1052-2HB08-7BA1) (All versions >= V8.3). Affected devices are vulnerable to an electromagnetic fault injection. This could allow an attacker to dump and debug the firmware, including the manipulation of memory. Further actions could allow to inject public keys of custom created key pairs which are then signed by the product CA. The generation of a custom certificate allows communication with, and impersonation of, any device of the same version.

Affected products

Version statuses are supplied by the assigning organization. Consult the original record for detailed ranges and platform conditions.

Siemens LOGO! 12/24RCE

Default version status: unknown

  • V8.3 to < *affected

Siemens LOGO! 12/24RCEo

Default version status: unknown

  • V8.3 to < *affected

Siemens LOGO! 230RCE

Default version status: unknown

  • V8.3 to < *affected

Siemens LOGO! 230RCEo

Default version status: unknown

  • V8.3 to < *affected

Siemens LOGO! 24CE

Default version status: unknown

  • V8.3 to < *affected

Siemens LOGO! 24CEo

Default version status: unknown

  • V8.3 to < *affected

Siemens LOGO! 24RCE

Default version status: unknown

  • V8.3 to < *affected

Siemens LOGO! 24RCEo

Default version status: unknown

  • V8.3 to < *affected

Siemens SIPLUS LOGO! 12/24RCE

Default version status: unknown

  • V8.3 to < *affected

Siemens SIPLUS LOGO! 12/24RCEo

Default version status: unknown

  • V8.3 to < *affected

Siemens SIPLUS LOGO! 230RCE

Default version status: unknown

  • V8.3 to < *affected

Siemens SIPLUS LOGO! 230RCEo

Default version status: unknown

  • V8.3 to < *affected

Siemens SIPLUS LOGO! 24CE

Default version status: unknown

  • V8.3 to < *affected

Siemens SIPLUS LOGO! 24CEo

Default version status: unknown

  • V8.3 to < *affected

Siemens SIPLUS LOGO! 24RCE

Default version status: unknown

  • V8.3 to < *affected

Siemens SIPLUS LOGO! 24RCEo

Default version status: unknown

  • V8.3 to < *affected

References