Description
Communication to the AMC2 uses a state-of-the-art cryptographic algorithm for symmetric encryption called Blowfish. An attacker could retrieve the key from the firmware to decrypt network traffic between the AMC2 and the host system. Thus, an attacker can exploit this vulnerability to decrypt and modify network traffic, decrypt and further investigate the device\'s firmware file, and change the device configuration. The attacker needs to have access to the local network, typically even the same subnet.
Affected products
Version statuses are supplied by the assigning organization. Consult the original record for detailed ranges and platform conditions.
Bosch AMS
unspecified to < 4.0affected
Bosch APE
unspecified to ≤ 3.8.xaffected
Bosch BIS
unspecified to < 4.9.1affected
Bosch AMC2
allaffected