Skip to content
CVE PROGRAM SOURCE RECORD8.2 High

CVE-2018-16557

A vulnerability has been identified in SIMATIC S7-400 CPU 412-1 DP V7 (All versions), SIMATIC S7-400 CPU 412-2 DP V7 (All versions), SIMATIC S7-400 CPU 414-2 DP V7 (All versions

Description

A vulnerability has been identified in SIMATIC S7-400 CPU 412-1 DP V7 (All versions), SIMATIC S7-400 CPU 412-2 DP V7 (All versions), SIMATIC S7-400 CPU 414-2 DP V7 (All versions), SIMATIC S7-400 CPU 414-3 DP V7 (All versions), SIMATIC S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 414F-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 416-2 DP V7 (All versions), SIMATIC S7-400 CPU 416-3 DP V7 (All versions), SIMATIC S7-400 CPU 416-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 416F-2 DP V7 (All versions), SIMATIC S7-400 CPU 416F-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 417-4 DP V7 (All versions), SIMATIC S7-400 CPU 412-2 PN V7 (All versions < V7.0.3), SIMATIC S7-400 H V4.5 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 H V6 CPU family (incl. SIPLUS variants) (All versions < V6.0.9), SIMATIC S7-400 PN/DP V6 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-410 CPU family (incl. SIPLUS variants) (All versions < V8.2.1), SIPLUS S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3), SIPLUS S7-400 CPU 416-3 PN/DP V7 (All versions < V7.0.3), SIPLUS S7-400 CPU 416-3 V7 (All versions), SIPLUS S7-400 CPU 417-4 V7 (All versions). Sending of specially crafted packets to port 102/tcp via Ethernet interface via PROFIBUS or Multi Point Interfaces (MPI) could cause a denial of service condition on affected devices. Flashing with a firmware image may be required to recover the CPU. Successful exploitation requires an attacker to have network access to port 102/tcp via Ethernet interface or to be able to send messages via PROFIBUS or Multi Point Interfaces (MPI) to the device. No user interaction is required. If no access protection is configured, no privileges are required to exploit the security vulnerability. The vulnerability could allow causing a denial of service condition of the core functionality of the CPU, compromising the availability of the system.

Affected products

Version statuses are supplied by the assigning organization. Consult the original record for detailed ranges and platform conditions.

Siemens SIMATIC S7-400 CPU 412-1 DP V7

Default version status: unknown

  • All versionsaffected

Siemens SIMATIC S7-400 CPU 412-2 DP V7

Default version status: unknown

  • All versionsaffected

Siemens SIMATIC S7-400 CPU 414-2 DP V7

Default version status: unknown

  • All versionsaffected

Siemens SIMATIC S7-400 CPU 414-3 DP V7

Default version status: unknown

  • All versionsaffected

Siemens SIMATIC S7-400 CPU 414-3 PN/DP V7

Default version status: unknown

  • All versions < V7.0.3affected

Siemens SIMATIC S7-400 CPU 414F-3 PN/DP V7

Default version status: unknown

  • All versions < V7.0.3affected

Siemens SIMATIC S7-400 CPU 416-2 DP V7

Default version status: unknown

  • All versionsaffected

Siemens SIMATIC S7-400 CPU 416-3 DP V7

Default version status: unknown

  • All versionsaffected

Siemens SIMATIC S7-400 CPU 416-3 PN/DP V7

Default version status: unknown

  • All versions < V7.0.3affected

Siemens SIMATIC S7-400 CPU 416F-2 DP V7

Default version status: unknown

  • All versionsaffected

Siemens SIMATIC S7-400 CPU 416F-3 PN/DP V7

Default version status: unknown

  • All versions < V7.0.3affected

Siemens SIMATIC S7-400 CPU 417-4 DP V7

Default version status: unknown

  • All versionsaffected

Siemens SIMATIC S7-400 CPU 412-2 PN V7

Default version status: unknown

  • All versions < V7.0.3affected

Siemens SIMATIC S7-400 H V4.5 and below CPU family (incl. SIPLUS variants)

Default version status: unknown

  • All versionsaffected

Siemens SIMATIC S7-400 H V6 CPU family (incl. SIPLUS variants)

Default version status: unknown

  • All versions < V6.0.9affected

Siemens SIMATIC S7-400 PN/DP V6 and below CPU family (incl. SIPLUS variants)

Default version status: unknown

  • All versionsaffected

Siemens SIMATIC S7-410 CPU family (incl. SIPLUS variants)

Default version status: unknown

  • All versions < V8.2.1affected

Siemens SIPLUS S7-400 CPU 414-3 PN/DP V7

Default version status: unknown

  • All versions < V7.0.3affected

Siemens SIPLUS S7-400 CPU 416-3 PN/DP V7

Default version status: unknown

  • All versions < V7.0.3affected

Siemens SIPLUS S7-400 CPU 416-3 V7

Default version status: unknown

  • All versionsaffected

Siemens SIPLUS S7-400 CPU 417-4 V7

Default version status: unknown

  • All versionsaffected

References