{"id":"CVE-2026-60063","state":"PUBLISHED","title":"AutomationDirect Productivity Suite Out-of-bounds Write","description":"An out-of-bounds write vulnerability in the Productivity Suite allows a \nlocal attacker to trigger kernel memory corruption via a crafted IOCTL \nrequest, potentially resulting in privilege escalation or system \ninstability.","publishedAt":"2026-07-16T19:59:16.196Z","updatedAt":"2026-07-17T13:25:08.344Z","severity":{"score":7.3,"label":"High","version":"4.0","vector":"CVSS:4.0/AV:L/AC:H/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N","source":"icscert"},"assigner":"icscert","products":["AutomationDirect Productivity Suite"],"affected":[{"vendor":"AutomationDirect","product":"Productivity Suite","defaultStatus":"unaffected","versions":[{"version":"0","status":"affected","lessThanOrEqual":"v4.6.2.2","versionType":"custom"},{"version":"v4.7.0.47","status":"unaffected"}]}],"references":["https://www.automationdirect.com/support/software-downloads","https://www.cisa.gov/news-events/ics-advisories/icsa-26-197-04","https://github.com/cisagov/CSAF/blob/develop/csaf_files/OT/white/2026/icsa-26-197-04.json"],"weaknesses":["CWE-787"],"ingestedAt":"2026-10-29T20:12:32.778Z","source":{"repository":"CVEProject/cvelistV5","path":"cves/2026/60xxx/CVE-2026-60063.json","commit":"556c9d3a8cd17e218bb8e452ba7cd619a384ff47"},"raw":{"dataType":"CVE_RECORD","dataVersion":"5.2","cveMetadata":{"cveId":"CVE-2026-60063","state":"PUBLISHED","datePublished":"2026-07-16T19:59:16.196Z","dateUpdated":"2026-07-17T13:25:08.344Z","assignerShortName":"icscert","assignerOrgId":"7d14cffa-0d7d-4270-9dc0-52cabd5a23a6","dateReserved":"2026-07-09T15:00:24.526Z"},"containers":{"cna":{"title":"AutomationDirect Productivity Suite Out-of-bounds Write","descriptions":[{"lang":"en","value":"An out-of-bounds write vulnerability in the Productivity Suite allows a \nlocal attacker to trigger kernel memory corruption via a crafted IOCTL \nrequest, potentially resulting in privilege escalation or system \ninstability."}],"affected":[{"vendor":"AutomationDirect","product":"Productivity Suite","defaultStatus":"unaffected","versions":[{"version":"0","status":"affected","lessThanOrEqual":"v4.6.2.2","versionType":"custom"},{"version":"v4.7.0.47","status":"unaffected"}]}],"references":[{"url":"https://www.automationdirect.com/support/software-downloads"},{"url":"https://www.cisa.gov/news-events/ics-advisories/icsa-26-197-04"},{"url":"https://github.com/cisagov/CSAF/blob/develop/csaf_files/OT/white/2026/icsa-26-197-04.json"}],"metrics":[{"format":"CVSS","scenarios":[{"lang":"en","value":"GENERAL"}],"cvssV3_1":{"version":"3.1","attackVector":"LOCAL","attackComplexity":"HIGH","privilegesRequired":"LOW","userInteraction":"NONE","scope":"UNCHANGED","confidentialityImpact":"HIGH","integrityImpact":"HIGH","availabilityImpact":"HIGH","baseSeverity":"HIGH","baseScore":7,"vectorString":"CVSS:3.1/AV:L/AC:H/PR:L/UI:N/S:U/C:H/I:H/A:H"}},{"format":"CVSS","scenarios":[{"lang":"en","value":"GENERAL"}],"cvssV4_0":{"attackVector":"LOCAL","attackComplexity":"HIGH","attackRequirements":"NONE","privilegesRequired":"LOW","userInteraction":"NONE","vulnConfidentialityImpact":"HIGH","subConfidentialityImpact":"NONE","vulnIntegrityImpact":"HIGH","subIntegrityImpact":"NONE","vulnAvailabilityImpact":"HIGH","subAvailabilityImpact":"NONE","exploitMaturity":"NOT_DEFINED","Safety":"NOT_DEFINED","Automatable":"NOT_DEFINED","Recovery":"NOT_DEFINED","valueDensity":"NOT_DEFINED","vulnerabilityResponseEffort":"NOT_DEFINED","providerUrgency":"NOT_DEFINED","version":"4.0","baseSeverity":"HIGH","baseScore":7.3,"vectorString":"CVSS:4.0/AV:L/AC:H/AT:N/PR:L/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N"}}],"problemTypes":[{"descriptions":[{"cweId":"CWE-787","lang":"en","description":"CWE-787","type":"CWE"}]}],"providerMetadata":{"shortName":"icscert","orgId":"7d14cffa-0d7d-4270-9dc0-52cabd5a23a6","dateUpdated":"2026-07-16T19:59:16.196Z"},"workarounds":[{"lang":"en","value":"If the update cannot be applied right away, the following \ncompensating controls are recommended until the upgrade can be \nperformed.\n\n\n  *  Disconnect the engineering workstation from external networks (e.g., the internet or corporate LAN) to reduce exposure.\n  *  Use only trusted, dedicated internal networks or air-gapped systems for device communication.\n  *  Restrict both physical and logical access to authorized personnel only.\n  *  Configure whitelisting so that only trusted, pre-approved applications are allowed to run. Block any unauthorized software.\n  *  Use antivirus or EDR tools and configure host-based firewalls to block unauthorized access attempts.\n  *  Enable and regularly review system logs to detect suspicious or unauthorized activity.\n  *  Maintain secure, tested backups of the PLC and its configurations to minimize downtime in case of an incident.\n  *  Continuously evaluate risks associated with running outdated firmware and adjust compensating measures accordingly.","supportingMedia":[{"type":"text/html","base64":false,"value":"<p>If the update cannot be applied right away, the following \ncompensating controls are recommended until the upgrade can be \nperformed.<br></p><ul><li>Disconnect the engineering workstation from external networks (e.g., the internet or corporate LAN) to reduce exposure.</li><li>Use only trusted, dedicated internal networks or air-gapped systems for device communication.</li><li>Restrict both physical and logical access to authorized personnel only.</li><li>Configure whitelisting so that only trusted, pre-approved applications are allowed to run. Block any unauthorized software.</li><li>Use antivirus or EDR tools and configure host-based firewalls to block unauthorized access attempts.</li><li>Enable and regularly review system logs to detect suspicious or unauthorized activity.</li><li>Maintain secure, tested backups of the PLC and its configurations to minimize downtime in case of an incident.</li><li>Continuously evaluate risks associated with running outdated firmware and adjust compensating measures accordingly.</li></ul>"}]}],"solutions":[{"lang":"en","value":"AutomationDirect recommends that users update Productivity suite to \nv4.7.0.47 and above \n https://www.automationdirect.com/support/software-downloads","supportingMedia":[{"type":"text/html","base64":false,"value":"AutomationDirect recommends that users update Productivity suite to \nv4.7.0.47 and above&nbsp;<br><a href=\"https://www.automationdirect.com/support/software-downloads\">https://www.automationdirect.com/support/software-downloads</a>"}]}],"credits":[{"lang":"en","value":"Luca Borzacchiello of Nozomi Networks reported this vulnerability to CISA.","type":"finder"}],"source":{"advisory":"ICSA-26-197-04","discovery":"EXTERNAL"},"x_generator":{"engine":"Vulnogram 1.0.2"}},"adp":[{"title":"CISA ADP Vulnrichment","metrics":[{"other":{"type":"ssvc","content":{"timestamp":"2026-07-17T13:24:44.620879Z","id":"CVE-2026-60063","options":[{"Exploitation":"none"},{"Automatable":"no"},{"Technical Impact":"total"}],"role":"CISA Coordinator","version":"2.0.3"}}}],"providerMetadata":{"shortName":"CISA-ADP","orgId":"134c704f-9b21-4f2e-91b3-4a467353bcc0","dateUpdated":"2026-07-17T13:25:08.344Z"}}]}}}