{"id":"CVE-2025-7972","state":"PUBLISHED","title":"Rockwell Automation FactoryTalk® Linx Network Browser Security Bypass Vulnerability","description":"A security issue exists within the FactoryTalk Linx Network Browser. By modifying the process.env.NODE_ENV to ‘development’, the attacker can disable FTSP token validation. This bypass allows access to create, update, and delete FTLinx drivers.","publishedAt":"2025-08-14T14:47:46.316Z","updatedAt":"2025-08-14T15:08:22.952Z","severity":{"score":8.4,"label":"High","version":"4.0","vector":"CVSS:4.0/AV:L/AC:L/AT:N/PR:N/UI:N/VC:N/VI:H/VA:H/SC:N/SI:H/SA:H","source":"Rockwell"},"assigner":"Rockwell","products":["Rockwell Automation FactoryTalk® Linx"],"affected":[{"vendor":"Rockwell Automation","product":"FactoryTalk® Linx","defaultStatus":"unaffected","versions":[{"version":"All prior to 6.50","status":"affected"}]}],"references":["https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1735.html"],"weaknesses":["CWE-286"],"ingestedAt":"2026-10-29T20:10:04.440Z","source":{"repository":"CVEProject/cvelistV5","path":"cves/2025/7xxx/CVE-2025-7972.json","commit":"556c9d3a8cd17e218bb8e452ba7cd619a384ff47"},"raw":{"dataType":"CVE_RECORD","dataVersion":"5.1","cveMetadata":{"cveId":"CVE-2025-7972","state":"PUBLISHED","datePublished":"2025-08-14T14:47:46.316Z","dateUpdated":"2025-08-14T15:08:22.952Z","assignerShortName":"Rockwell","assignerOrgId":"b73dd486-f505-4403-b634-40b078b177f0","dateReserved":"2025-07-21T19:25:20.271Z"},"containers":{"cna":{"title":"Rockwell Automation FactoryTalk® Linx Network Browser Security Bypass Vulnerability","descriptions":[{"lang":"en","value":"A security issue exists within the FactoryTalk Linx Network Browser. By modifying the process.env.NODE_ENV to ‘development’, the attacker can disable FTSP token validation. This bypass allows access to create, update, and delete FTLinx drivers."}],"affected":[{"vendor":"Rockwell Automation","product":"FactoryTalk® Linx","defaultStatus":"unaffected","versions":[{"version":"All prior to 6.50","status":"affected"}]}],"references":[{"url":"https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1735.html"}],"metrics":[{"cvssV4_0":{"Automatable":"NOT_DEFINED","Recovery":"NOT_DEFINED","Safety":"NOT_DEFINED","attackComplexity":"LOW","attackRequirements":"NONE","attackVector":"LOCAL","baseScore":8.4,"baseSeverity":"HIGH","privilegesRequired":"NONE","providerUrgency":"NOT_DEFINED","subAvailabilityImpact":"HIGH","subConfidentialityImpact":"NONE","subIntegrityImpact":"HIGH","userInteraction":"NONE","valueDensity":"NOT_DEFINED","vectorString":"CVSS:4.0/AV:L/AC:L/AT:N/PR:N/UI:N/VC:N/VI:H/VA:H/SC:N/SI:H/SA:H","version":"4.0","vulnAvailabilityImpact":"HIGH","vulnConfidentialityImpact":"NONE","vulnIntegrityImpact":"HIGH","vulnerabilityResponseEffort":"NOT_DEFINED"},"format":"CVSS","scenarios":[{"lang":"en","value":"GENERAL"}]}],"problemTypes":[{"descriptions":[{"cweId":"CWE-286","description":"CWE-286: Incorrect User Management","lang":"en","type":"CWE"}]}],"providerMetadata":{"shortName":"Rockwell","orgId":"b73dd486-f505-4403-b634-40b078b177f0","dateUpdated":"2025-08-14T14:54:29.154Z"},"solutions":[{"lang":"en","supportingMedia":[{"base64":false,"type":"text/html","value":"Upgrade to version 6.50 or later."}],"value":"Upgrade to version 6.50 or later."}],"source":{"advisory":"SD1735","discovery":"INTERNAL"},"x_generator":{"engine":"Vulnogram 0.2.0"}},"adp":[{"title":"CISA ADP Vulnrichment","metrics":[{"other":{"type":"ssvc","content":{"timestamp":"2025-08-14T15:06:45.964707Z","id":"CVE-2025-7972","options":[{"Exploitation":"none"},{"Automatable":"no"},{"Technical Impact":"partial"}],"role":"CISA Coordinator","version":"2.0.3"}}}],"providerMetadata":{"shortName":"CISA-ADP","orgId":"134c704f-9b21-4f2e-91b3-4a467353bcc0","dateUpdated":"2025-08-14T15:08:22.952Z"}}]}}}