{"id":"CVE-2024-7515","state":"PUBLISHED","title":"Rockwell Automation ControlLogix/GuardLogix 5580 and CompactLogix/Compact GuardLogix® 5380 Controller Denial-of-Service Vulnerability via Input Validation","description":"CVE-2024-7515 IMPACT\n\nA denial-of-service vulnerability exists in the affected products. A malformed PTP management packet can cause a major nonrecoverable fault in the controller.","publishedAt":"2024-08-14T19:40:20.990Z","updatedAt":"2024-08-14T19:59:57.056Z","severity":{"score":8.7,"label":"High","version":"4.0","vector":"CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N","source":"Rockwell"},"assigner":"Rockwell","products":["Rockwell Automation CompactLogix 5380 (5069-L3z)","Rockwell Automation ControlLogix® 5580 (1756- L8z)","Rockwell Automation GuardLogix 5580 (1756- L8zS)","Rockwell Automation Compact GuardLogix 5380 (5069 – L3zS2)","Rockwell Automation CompactLogix 5480 (5069-L4)"],"affected":[{"vendor":"Rockwell Automation","product":"CompactLogix 5380 (5069-L3z)","defaultStatus":"unaffected","versions":[{"version":"28.011","status":"affected"}]},{"vendor":"Rockwell Automation","product":"ControlLogix® 5580 (1756- L8z)","defaultStatus":"unaffected","versions":[{"version":"28.011","status":"affected"}]},{"vendor":"Rockwell Automation","product":"GuardLogix 5580 (1756- L8zS)","defaultStatus":"unaffected","versions":[{"version":"28.011","status":"affected"}]},{"vendor":"Rockwell Automation","product":"Compact GuardLogix 5380 (5069 – L3zS2)","defaultStatus":"unaffected","versions":[{"version":"28.011","status":"affected"}]},{"vendor":"Rockwell Automation","product":"CompactLogix 5480 (5069-L4)","defaultStatus":"unaffected","versions":[{"version":"28.011","status":"affected"}]}],"references":["https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD%201686.html"],"weaknesses":["CWE-20"],"ingestedAt":"2026-10-29T20:08:20.985Z","source":{"repository":"CVEProject/cvelistV5","path":"cves/2024/7xxx/CVE-2024-7515.json","commit":"556c9d3a8cd17e218bb8e452ba7cd619a384ff47"},"raw":{"dataType":"CVE_RECORD","dataVersion":"5.1","cveMetadata":{"cveId":"CVE-2024-7515","state":"PUBLISHED","datePublished":"2024-08-14T19:40:20.990Z","dateUpdated":"2024-08-14T19:59:57.056Z","assignerShortName":"Rockwell","assignerOrgId":"b73dd486-f505-4403-b634-40b078b177f0","dateReserved":"2024-08-05T20:19:29.235Z"},"containers":{"cna":{"title":"Rockwell Automation ControlLogix/GuardLogix 5580 and CompactLogix/Compact GuardLogix® 5380 Controller Denial-of-Service Vulnerability via Input Validation","descriptions":[{"lang":"en","value":"CVE-2024-7515 IMPACT\n\nA denial-of-service vulnerability exists in the affected products. A malformed PTP management packet can cause a major nonrecoverable fault in the controller."}],"affected":[{"vendor":"Rockwell Automation","product":"CompactLogix 5380 (5069-L3z)","defaultStatus":"unaffected","versions":[{"version":"28.011","status":"affected"}]},{"vendor":"Rockwell Automation","product":"ControlLogix® 5580 (1756- L8z)","defaultStatus":"unaffected","versions":[{"version":"28.011","status":"affected"}]},{"vendor":"Rockwell Automation","product":"GuardLogix 5580 (1756- L8zS)","defaultStatus":"unaffected","versions":[{"version":"28.011","status":"affected"}]},{"vendor":"Rockwell Automation","product":"Compact GuardLogix 5380 (5069 – L3zS2)","defaultStatus":"unaffected","versions":[{"version":"28.011","status":"affected"}]},{"vendor":"Rockwell Automation","product":"CompactLogix 5480 (5069-L4)","defaultStatus":"unaffected","versions":[{"version":"28.011","status":"affected"}]}],"references":[{"url":"https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD%201686.html"}],"metrics":[{"cvssV4_0":{"Automatable":"NOT_DEFINED","Recovery":"NOT_DEFINED","Safety":"NOT_DEFINED","attackComplexity":"LOW","attackRequirements":"NONE","attackVector":"NETWORK","baseScore":8.7,"baseSeverity":"HIGH","privilegesRequired":"NONE","providerUrgency":"NOT_DEFINED","subAvailabilityImpact":"NONE","subConfidentialityImpact":"NONE","subIntegrityImpact":"NONE","userInteraction":"NONE","valueDensity":"NOT_DEFINED","vectorString":"CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N","version":"4.0","vulnAvailabilityImpact":"HIGH","vulnConfidentialityImpact":"NONE","vulnIntegrityImpact":"NONE","vulnerabilityResponseEffort":"NOT_DEFINED"},"format":"CVSS","scenarios":[{"lang":"en","value":"GENERAL"}]}],"problemTypes":[{"descriptions":[{"cweId":"CWE-20","description":"CWE-20 Improper Input Validation","lang":"en","type":"CWE"}]}],"providerMetadata":{"shortName":"Rockwell","orgId":"b73dd486-f505-4403-b634-40b078b177f0","dateUpdated":"2024-08-14T19:40:20.990Z"},"datePublic":"2024-08-13T13:00:00.000Z","impacts":[{"capecId":"CAPEC-153","descriptions":[{"lang":"en","value":"CAPEC-153 Input Data Manipulation"}]}],"solutions":[{"lang":"en","supportingMedia":[{"base64":false,"type":"text/html","value":"Upgrade to:&nbsp;\n\n<span style=\"background-color: rgb(255, 255, 255);\">v36.011, v35.013, v34.014</span>"}],"value":"Upgrade to: \n\nv36.011, v35.013, v34.014"}],"source":{"discovery":"INTERNAL"},"workarounds":[{"lang":"en","supportingMedia":[{"base64":false,"type":"text/html","value":"<p>If PTP messages are not used, block at the network level, port UDP 319/320</p>"}],"value":"If PTP messages are not used, block at the network level, port UDP 319/320"}],"x_generator":{"engine":"Vulnogram 0.2.0"}},"adp":[{"title":"CISA ADP Vulnrichment","affected":[{"vendor":"rockwellautomation","product":"compactlogix_5380_firmware","defaultStatus":"unknown","versions":[{"version":"v28.011","status":"affected"}],"cpes":["cpe:2.3:o:rockwellautomation:compactlogix_5380_firmware:v28.011:*:*:*:*:*:*:*"]},{"vendor":"rockwellautomation","product":"controllogix_5580_firmware","defaultStatus":"unknown","versions":[{"version":"v28.011","status":"affected"}],"cpes":["cpe:2.3:o:rockwellautomation:controllogix_5580_firmware:v28.011:*:*:*:*:*:*:*"]},{"vendor":"rockwellautomation","product":"guardlogix_5580_firmware","defaultStatus":"unknown","versions":[{"version":"28.011","status":"affected"}],"cpes":["cpe:2.3:o:rockwellautomation:guardlogix_5580_firmware:28.011:*:*:*:*:*:*:*"]},{"vendor":"rockwellautomation","product":"compact_guardlogix_5380_firmware","defaultStatus":"unknown","versions":[{"version":"28.011","status":"affected"}],"cpes":["cpe:2.3:o:rockwellautomation:compact_guardlogix_5380_firmware:28.011:*:*:*:*:*:*:*"]},{"vendor":"rockwellautomation","product":"compactlogix_5480_firmware","defaultStatus":"unknown","versions":[{"version":"28.011","status":"affected"}],"cpes":["cpe:2.3:o:rockwellautomation:compactlogix_5480_firmware:28.011:*:*:*:*:*:*:*"]}],"metrics":[{"other":{"type":"ssvc","content":{"timestamp":"2024-08-14T19:54:17.968076Z","id":"CVE-2024-7515","options":[{"Exploitation":"none"},{"Automatable":"yes"},{"Technical Impact":"partial"}],"role":"CISA Coordinator","version":"2.0.3"}}}],"providerMetadata":{"shortName":"CISA-ADP","orgId":"134c704f-9b21-4f2e-91b3-4a467353bcc0","dateUpdated":"2024-08-14T19:59:57.056Z"}}]}}}