{"id":"CVE-2022-3166","state":"PUBLISHED","title":"MicroLogix 1100 & 1400 Product Web Server Application Vulnerable to Denial-Of-Service Condition Attack","description":"\nRockwell Automation was made aware that the webservers of the Micrologix 1100 and 1400 controllers contain a vulnerability that may lead to a denial-of-service condition. The security vulnerability could be exploited by an attacker with network access to the affected systems by sending TCP packets to webserver and closing it abruptly which would cause a denial-of-service condition for the web server application on the device\n\n","publishedAt":"2022-12-16T19:59:25.261Z","updatedAt":"2025-04-17T15:30:27.677Z","severity":{"score":7.5,"label":"High","version":"3.1","vector":"CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H","source":"Rockwell"},"assigner":"Rockwell","products":["Rockwell Automation MicroLogix 1100","Rockwell Automation MicroLogix 1400-B/C","Rockwell Automation MicroLogix 1400-A"],"affected":[{"vendor":"Rockwell Automation","product":"MicroLogix 1100","defaultStatus":"unaffected","versions":[{"version":"All","status":"affected"}]},{"vendor":"Rockwell Automation","product":"MicroLogix 1400-B/C","defaultStatus":"unaffected","versions":[{"version":"21.007 and below","status":"affected"}]},{"vendor":"Rockwell Automation","product":"MicroLogix 1400-A","defaultStatus":"unaffected","versions":[{"version":"7.000 and below","status":"affected"}]}],"references":["https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1137678"],"weaknesses":["CWE-924"],"ingestedAt":"2026-10-29T19:50:32.060Z","source":{"repository":"CVEProject/cvelistV5","path":"cves/2022/3xxx/CVE-2022-3166.json","commit":"556c9d3a8cd17e218bb8e452ba7cd619a384ff47"},"raw":{"dataType":"CVE_RECORD","dataVersion":"5.1","cveMetadata":{"cveId":"CVE-2022-3166","state":"PUBLISHED","datePublished":"2022-12-16T19:59:25.261Z","dateUpdated":"2025-04-17T15:30:27.677Z","assignerShortName":"Rockwell","assignerOrgId":"b73dd486-f505-4403-b634-40b078b177f0","requesterUserId":"20b06643-9bf3-4d1d-a98d-f8db99f95a31","dateReserved":"2022-09-08T13:39:09.263Z"},"containers":{"cna":{"title":"MicroLogix 1100 & 1400 Product Web Server Application Vulnerable to Denial-Of-Service Condition Attack","descriptions":[{"lang":"en","value":"\nRockwell Automation was made aware that the webservers of the Micrologix 1100 and 1400 controllers contain a vulnerability that may lead to a denial-of-service condition. The security vulnerability could be exploited by an attacker with network access to the affected systems by sending TCP packets to webserver and closing it abruptly which would cause a denial-of-service condition for the web server application on the device\n\n"}],"affected":[{"vendor":"Rockwell Automation","product":"MicroLogix 1100","defaultStatus":"unaffected","versions":[{"version":"All","status":"affected"}]},{"vendor":"Rockwell Automation","product":"MicroLogix 1400-B/C","defaultStatus":"unaffected","versions":[{"version":"21.007 and below","status":"affected"}]},{"vendor":"Rockwell Automation","product":"MicroLogix 1400-A","defaultStatus":"unaffected","versions":[{"version":"7.000 and below","status":"affected"}]}],"references":[{"url":"https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1137678"}],"metrics":[{"cvssV3_1":{"attackComplexity":"LOW","attackVector":"NETWORK","availabilityImpact":"HIGH","baseScore":7.5,"baseSeverity":"HIGH","confidentialityImpact":"NONE","integrityImpact":"NONE","privilegesRequired":"NONE","scope":"UNCHANGED","userInteraction":"NONE","vectorString":"CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H","version":"3.1"},"format":"CVSS","scenarios":[{"lang":"en","value":"GENERAL"}]}],"problemTypes":[{"descriptions":[{"cweId":"CWE-924","description":"CWE-924 Improper Enforcement of Message Integrity During Transmission in a Communication Channel","lang":"en","type":"CWE"}]}],"providerMetadata":{"shortName":"Rockwell","orgId":"b73dd486-f505-4403-b634-40b078b177f0","dateUpdated":"2022-12-19T14:08:16.124Z"},"credits":[{"lang":"en","type":"finder","user":"00000000-0000-4000-9000-000000000000","value":"Parul Sindhwad and Dr. Faruk Kazi of CoE-CNDS Lab, VJTI, Mumbai, India reported this vulnerability to Rockwell Automation"}],"datePublic":"2022-12-13T15:00:00.000Z","impacts":[{"capecId":"CAPEC-176","descriptions":[{"lang":"en","value":"CAPEC-176 Configuration/Environment Manipulation"}]}],"source":{"discovery":"UNKNOWN"},"x_generator":{"engine":"Vulnogram 0.1.0-dev"}},"adp":[{"title":"CVE Program Container","references":[{"url":"https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1137678","tags":["x_transferred"]}],"providerMetadata":{"shortName":"CVE","orgId":"af854a3a-2127-422b-91ae-364da2661108","dateUpdated":"2024-08-03T01:00:10.526Z"}},{"title":"CISA ADP Vulnrichment","metrics":[{"other":{"type":"ssvc","content":{"timestamp":"2025-04-17T15:30:04.669128Z","id":"CVE-2022-3166","options":[{"Exploitation":"none"},{"Automatable":"yes"},{"Technical Impact":"partial"}],"role":"CISA Coordinator","version":"2.0.3"}}}],"providerMetadata":{"shortName":"CISA-ADP","orgId":"134c704f-9b21-4f2e-91b3-4a467353bcc0","dateUpdated":"2025-04-17T15:30:27.677Z"}}]}}}