{"id":"CVE-2022-30319","state":"PUBLISHED","title":"Saia Burgess Controls (SBC) PCD through 2022-05-06 allows Authentication bypass. According to FSCT-2022-0062, there is a Saia Burgess Controls (SBC) PCD S-Bus authentication bypass","description":"Saia Burgess Controls (SBC) PCD through 2022-05-06 allows Authentication bypass. According to FSCT-2022-0062, there is a Saia Burgess Controls (SBC) PCD S-Bus authentication bypass issue. The affected components are characterized as: S-Bus (5050/UDP) authentication. The potential impact is: Authentication bypass. The Saia Burgess Controls (SBC) PCD controllers utilize the S-Bus protocol (5050/UDP) for a variety of engineering purposes. It is possible to configure a password in order to restrict access to sensitive engineering functionality. Authentication functions on the basis of a MAC/IP whitelist with inactivity timeout to which an authenticated client's MAC/IP is stored. UDP traffic can be spoofed to bypass the whitelist-based access control. Since UDP is stateless, an attacker capable of passively observing traffic can spoof arbitrary messages using the MAC/IP of an authenticated client. This allows the attacker access to sensitive engineering functionality such as uploading/downloading control logic and manipulating controller configuration.","publishedAt":"2022-07-28T15:50:53.000Z","updatedAt":"2024-11-20T16:16:57.817Z","severity":null,"assigner":"mitre","products":["n/a n/a"],"affected":[{"vendor":"n/a","product":"n/a","versions":[{"version":"n/a","status":"affected"}]}],"references":["https://www.forescout.com/blog/","https://www.cisa.gov/uscert/ics/advisories/icsa-22-207-03"],"weaknesses":[],"ingestedAt":"2026-10-29T19:50:04.052Z","source":{"repository":"CVEProject/cvelistV5","path":"cves/2022/30xxx/CVE-2022-30319.json","commit":"556c9d3a8cd17e218bb8e452ba7cd619a384ff47"},"raw":{"dataType":"CVE_RECORD","dataVersion":"5.1","cveMetadata":{"cveId":"CVE-2022-30319","state":"PUBLISHED","datePublished":"2022-07-28T15:50:53.000Z","dateUpdated":"2024-11-20T16:16:57.817Z","assignerShortName":"mitre","assignerOrgId":"8254265b-2729-46b6-b9e3-3dfca2d5bfca","dateReserved":"2022-05-06T00:00:00.000Z"},"containers":{"cna":{"descriptions":[{"lang":"en","value":"Saia Burgess Controls (SBC) PCD through 2022-05-06 allows Authentication bypass. According to FSCT-2022-0062, there is a Saia Burgess Controls (SBC) PCD S-Bus authentication bypass issue. The affected components are characterized as: S-Bus (5050/UDP) authentication. The potential impact is: Authentication bypass. The Saia Burgess Controls (SBC) PCD controllers utilize the S-Bus protocol (5050/UDP) for a variety of engineering purposes. It is possible to configure a password in order to restrict access to sensitive engineering functionality. Authentication functions on the basis of a MAC/IP whitelist with inactivity timeout to which an authenticated client's MAC/IP is stored. UDP traffic can be spoofed to bypass the whitelist-based access control. Since UDP is stateless, an attacker capable of passively observing traffic can spoof arbitrary messages using the MAC/IP of an authenticated client. This allows the attacker access to sensitive engineering functionality such as uploading/downloading control logic and manipulating controller configuration."}],"affected":[{"vendor":"n/a","product":"n/a","versions":[{"version":"n/a","status":"affected"}]}],"references":[{"url":"https://www.forescout.com/blog/","tags":["x_refsource_MISC"]},{"url":"https://www.cisa.gov/uscert/ics/advisories/icsa-22-207-03","tags":["x_refsource_MISC"]}],"problemTypes":[{"descriptions":[{"description":"n/a","lang":"en","type":"text"}]}],"providerMetadata":{"shortName":"mitre","dateUpdated":"2022-07-28T15:50:53.000Z","orgId":"8254265b-2729-46b6-b9e3-3dfca2d5bfca"},"x_legacyV4Record":{"CVE_data_meta":{"ASSIGNER":"cve@mitre.org","ID":"CVE-2022-30319","STATE":"PUBLIC"},"affects":{"vendor":{"vendor_data":[{"product":{"product_data":[{"product_name":"n/a","version":{"version_data":[{"version_value":"n/a"}]}}]},"vendor_name":"n/a"}]}},"data_format":"MITRE","data_type":"CVE","data_version":"4.0","description":{"description_data":[{"lang":"eng","value":"Saia Burgess Controls (SBC) PCD through 2022-05-06 allows Authentication bypass. According to FSCT-2022-0062, there is a Saia Burgess Controls (SBC) PCD S-Bus authentication bypass issue. The affected components are characterized as: S-Bus (5050/UDP) authentication. The potential impact is: Authentication bypass. The Saia Burgess Controls (SBC) PCD controllers utilize the S-Bus protocol (5050/UDP) for a variety of engineering purposes. It is possible to configure a password in order to restrict access to sensitive engineering functionality. Authentication functions on the basis of a MAC/IP whitelist with inactivity timeout to which an authenticated client's MAC/IP is stored. UDP traffic can be spoofed to bypass the whitelist-based access control. Since UDP is stateless, an attacker capable of passively observing traffic can spoof arbitrary messages using the MAC/IP of an authenticated client. This allows the attacker access to sensitive engineering functionality such as uploading/downloading control logic and manipulating controller configuration."}]},"problemtype":{"problemtype_data":[{"description":[{"lang":"eng","value":"n/a"}]}]},"references":{"reference_data":[{"name":"https://www.forescout.com/blog/","refsource":"MISC","url":"https://www.forescout.com/blog/"},{"name":"https://www.cisa.gov/uscert/ics/advisories/icsa-22-207-03","refsource":"MISC","url":"https://www.cisa.gov/uscert/ics/advisories/icsa-22-207-03"}]}}},"adp":[{"title":"CVE Program Container","references":[{"url":"https://www.forescout.com/blog/","tags":["x_refsource_MISC","x_transferred"]},{"url":"https://www.cisa.gov/uscert/ics/advisories/icsa-22-207-03","tags":["x_refsource_MISC","x_transferred"]}],"providerMetadata":{"shortName":"CVE","orgId":"af854a3a-2127-422b-91ae-364da2661108","dateUpdated":"2024-08-03T06:48:36.317Z"}},{"title":"CISA ADP Vulnrichment","metrics":[{"other":{"type":"ssvc","content":{"timestamp":"2024-11-20T16:16:14.742165Z","id":"CVE-2022-30319","options":[{"Exploitation":"none"},{"Automatable":"no"},{"Technical Impact":"total"}],"role":"CISA Coordinator","version":"2.0.3"}}}],"providerMetadata":{"shortName":"CISA-ADP","orgId":"134c704f-9b21-4f2e-91b3-4a467353bcc0","dateUpdated":"2024-11-20T16:16:57.817Z"}}]}}}