{"id":"CVE-2019-5637","state":"PUBLISHED","title":"Beckhoff TwinCAT Profinet Driver Divide-by-Zero Denial of Service","description":"When Beckhoff TwinCAT is configured to use the Profinet driver, a denial of service of the controller could be reached by sending a malformed UDP packet to the device. This issue affects TwinCAT 2 version 2304 (and prior) and TwinCAT 3.1 version 4204.0 (and prior).","publishedAt":"2019-11-21T19:16:13.344Z","updatedAt":"2024-09-17T01:35:41.695Z","severity":{"score":7.5,"label":"High","version":"3.1","vector":"CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H","source":"rapid7"},"assigner":"rapid7","products":["Beckhoff TwinCAT 2","Beckhoff TwinCAT 3.1"],"affected":[{"vendor":"Beckhoff","product":"TwinCAT 2","versions":[{"version":"2304","status":"affected","lessThanOrEqual":"2304","versionType":"custom"}]},{"vendor":"Beckhoff","product":"TwinCAT 3.1","versions":[{"version":"4204.0","status":"affected","lessThanOrEqual":"4204.0","versionType":"custom"}]}],"references":["https://blog.rapid7.com/2019/10/08/r7-2019-32-denial-of-service-vulnerabilities-in-beckhoff-twincat-plc-environment-fixed/","https://download.beckhoff.com/download/Document/product-security/Advisories/advisory-2019-007.pdf"],"weaknesses":["CWE-369"],"ingestedAt":"2026-10-29T19:46:04.126Z","source":{"repository":"CVEProject/cvelistV5","path":"cves/2019/5xxx/CVE-2019-5637.json","commit":"556c9d3a8cd17e218bb8e452ba7cd619a384ff47"},"raw":{"dataType":"CVE_RECORD","dataVersion":"5.1","cveMetadata":{"cveId":"CVE-2019-5637","state":"PUBLISHED","datePublished":"2019-11-21T19:16:13.344Z","dateUpdated":"2024-09-17T01:35:41.695Z","assignerShortName":"rapid7","assignerOrgId":"9974b330-7714-4307-a722-5648477acda7","dateReserved":"2019-01-07T00:00:00.000Z"},"containers":{"cna":{"title":"Beckhoff TwinCAT Profinet Driver Divide-by-Zero Denial of Service","descriptions":[{"lang":"en","value":"When Beckhoff TwinCAT is configured to use the Profinet driver, a denial of service of the controller could be reached by sending a malformed UDP packet to the device. This issue affects TwinCAT 2 version 2304 (and prior) and TwinCAT 3.1 version 4204.0 (and prior)."}],"affected":[{"vendor":"Beckhoff","product":"TwinCAT 2","versions":[{"version":"2304","status":"affected","lessThanOrEqual":"2304","versionType":"custom"}]},{"vendor":"Beckhoff","product":"TwinCAT 3.1","versions":[{"version":"4204.0","status":"affected","lessThanOrEqual":"4204.0","versionType":"custom"}]}],"references":[{"url":"https://blog.rapid7.com/2019/10/08/r7-2019-32-denial-of-service-vulnerabilities-in-beckhoff-twincat-plc-environment-fixed/","tags":["x_refsource_MISC"]},{"url":"https://download.beckhoff.com/download/Document/product-security/Advisories/advisory-2019-007.pdf","tags":["x_refsource_CONFIRM"]}],"metrics":[{"cvssV3_1":{"attackComplexity":"LOW","attackVector":"NETWORK","availabilityImpact":"HIGH","baseScore":7.5,"baseSeverity":"HIGH","confidentialityImpact":"NONE","integrityImpact":"NONE","privilegesRequired":"NONE","scope":"UNCHANGED","userInteraction":"NONE","vectorString":"CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H","version":"3.1"}}],"problemTypes":[{"descriptions":[{"cweId":"CWE-369","description":"CWE-369 Divide By Zero","lang":"en","type":"CWE"}]}],"providerMetadata":{"shortName":"rapid7","dateUpdated":"2020-02-04T22:58:40.000Z","orgId":"9974b330-7714-4307-a722-5648477acda7"},"credits":[{"lang":"en","value":"This issue was discovered, and reported to Rapid7, by Andreas Galauner at Rapid7. It is being disclosed in accordance with Rapid7's vulnerability disclosure policy (https://www.rapid7.com/disclosure/)."}],"datePublic":"2019-10-08T00:00:00.000Z","source":{"advisory":"R7-2019-32","discovery":"EXTERNAL"},"x_generator":{"engine":"Vulnogram 0.0.8"},"x_legacyV4Record":{"CVE_data_meta":{"ASSIGNER":"cve@rapid7.com","DATE_PUBLIC":"2019-10-08T14:05:00.000Z","ID":"CVE-2019-5637","STATE":"PUBLIC","TITLE":"Beckhoff TwinCAT Profinet Driver Divide-by-Zero Denial of Service"},"affects":{"vendor":{"vendor_data":[{"product":{"product_data":[{"product_name":"TwinCAT 2","version":{"version_data":[{"version_affected":"<=","version_name":"2304","version_value":"2304"}]}},{"product_name":"TwinCAT 3.1","version":{"version_data":[{"version_affected":"<=","version_name":"4204.0","version_value":"4204.0"}]}}]},"vendor_name":"Beckhoff"}]}},"credit":[{"lang":"eng","value":"This issue was discovered, and reported to Rapid7, by Andreas Galauner at Rapid7. It is being disclosed in accordance with Rapid7's vulnerability disclosure policy (https://www.rapid7.com/disclosure/)."}],"data_format":"MITRE","data_type":"CVE","data_version":"4.0","description":{"description_data":[{"lang":"eng","value":"When Beckhoff TwinCAT is configured to use the Profinet driver, a denial of service of the controller could be reached by sending a malformed UDP packet to the device. This issue affects TwinCAT 2 version 2304 (and prior) and TwinCAT 3.1 version 4204.0 (and prior)."}]},"generator":{"engine":"Vulnogram 0.0.8"},"impact":{"cvss":{"attackComplexity":"LOW","attackVector":"NETWORK","availabilityImpact":"HIGH","baseScore":7.5,"baseSeverity":"HIGH","confidentialityImpact":"NONE","integrityImpact":"NONE","privilegesRequired":"NONE","scope":"UNCHANGED","userInteraction":"NONE","vectorString":"CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H","version":"3.1"}},"problemtype":{"problemtype_data":[{"description":[{"lang":"eng","value":"CWE-369 Divide By Zero"}]}]},"references":{"reference_data":[{"name":"https://blog.rapid7.com/2019/10/08/r7-2019-32-denial-of-service-vulnerabilities-in-beckhoff-twincat-plc-environment-fixed/","refsource":"MISC","url":"https://blog.rapid7.com/2019/10/08/r7-2019-32-denial-of-service-vulnerabilities-in-beckhoff-twincat-plc-environment-fixed/"},{"name":"https://download.beckhoff.com/download/Document/product-security/Advisories/advisory-2019-007.pdf","refsource":"CONFIRM","url":"https://download.beckhoff.com/download/Document/product-security/Advisories/advisory-2019-007.pdf"}]},"source":{"advisory":"R7-2019-32","discovery":"EXTERNAL"}}},"adp":[{"title":"CVE Program Container","references":[{"url":"https://blog.rapid7.com/2019/10/08/r7-2019-32-denial-of-service-vulnerabilities-in-beckhoff-twincat-plc-environment-fixed/","tags":["x_refsource_MISC","x_transferred"]},{"url":"https://download.beckhoff.com/download/Document/product-security/Advisories/advisory-2019-007.pdf","tags":["x_refsource_CONFIRM","x_transferred"]}],"providerMetadata":{"shortName":"CVE","orgId":"af854a3a-2127-422b-91ae-364da2661108","dateUpdated":"2024-08-04T20:01:52.050Z"}}]}}}